Introduction
Fire
prevention measures propose to reduce the incidence of fires by eliminating
opportunities for ignition of flammable materials.
Flammable and Combustible
Materials
A. Substitution
Flammable
liquids sometimes may be substituted by relatively safe materials in order to
reduce the risk of fires. Any substituted material should be stable and
nontoxic and should either be nonflammable or have a high flashpoint.
B. Storage
Flammable
and combustible liquids require careful handling at all times. The proper
storage of flammable liquids within a work area is very important in order to
protect personnel from fire and other safety and health hazards.
1) Cabinets. Not more than 120 gallons
of Class I, Class II, and Class IIIA liquids may be stored in a storage
cabinet. Of this total, not more than 60 gallons may be Class I and II liquids.
Not more than three such cabinets (120 gallons each) may be located in a single
fire area except in an industrial area.
Table
1. Maximum allowable capacity of containers and portable tanks
|
Flammable
Liquids |
Combustible
Liquids |
|||
Container |
1A |
1B |
1C |
II |
III |
Glass
or approved plastic1 |
1
pt2 |
1
qt2 |
1
gal |
1
gal |
1
gal |
Metal
(Other than DOT drums) |
1
gal |
5
gal |
5
gal |
5
gal |
5
gal |
Safety
Cans |
2
gal |
5
gal |
5
gal |
5
gal |
5
gal |
Metal
drums (DOT specifications) |
60
gal |
60
gal |
60
gal |
60
gal |
60
gal |
Approved
portable tanks |
660
gal |
660
gal |
660
gal |
660
gal |
660
gal |
(1)
Nearest metric size is also acceptable for the glass and plastic |
2) Containers. The capacity of
flammable and combustible liquid containers will be in accordance with Table 1.
3) Storage Inside
Buildings. Where approved storage cabinets or rooms are
not provided, inside storage will comply with the following basic conditions:
a. The storage of any flammable or combustible
liquid shall not physically obstruct a means of egress from the building or
area.
b. Containers of flammable or combustible liquids
will remain tightly sealed except when transferred, poured or applied. Remove
only that portion of liquid in the storage container required to accomplish a
particular job.
c. If a flammable and combustible liquid storage
building is used, it will be a one-story building devoted principally to the
handling and storing of flammable or combustible liquids. The building will
have 2-hour fire-rated exterior walls having no opening within 10 feet of such
storage.
d. Flammable paints, oils, and varnishes in 1 or 5
gallon containers, used for building maintenance purposes, may be stored
temporarily in closed containers outside approved storage cabinets or room if
kept at the job site for less than 10 calendar days.
C. Ventilation
Every
inside storage room will be provided with a continuous mechanical exhaust
ventilation system. To prevent the accumulation of vapors, the location of both
the makeup and exhaust air openings will be arranged to provide, as far as
practical, air movement directly to the exterior of the building and if ducts
are used, they will not be used for any other purpose.
D. Elimination of Ignition Sources
All
nonessential ignition sources must be eliminated where flammable liquids are
used or stored. The following is a list of some of the more common potential
ignition sources:
E. Removal of Incompatibles
Materials
that can contribute to a flammable liquid fire should not be stored with
flammable liquids. Examples are oxidizers and organic peroxides, which, on
decomposition, can generate large amounts of oxygen.
F. Flammable Gases
Generally,
flammable gases pose the same type of fire hazards as flammable liquids and
their vapors. Many of the safeguards for flammable liquids also apply to
flammable gases, other properties such as toxicity, reactivity, and corrosivity
also must be taken into account. Also, a gas that is flammable could produce
toxic combustion products.
Fire
Extinguishers
A
portable fire extinguisher is a "first aid" device and is very
effective when used while the fire is small. The use of fire extinguisher that
matches the class of fire, by a person who is well trained, can save both lives
and property. Portable fire extinguishers must be installed in workplaces
regardless of other firefighting measures. The successful performance of a fire
extinguisher in a fire situation largely depends on its proper selection,
inspection, maintenance, and distribution.
A. Classification of Fires and Selection of
Extinguishers
Fires
are classified into four general categories depending on the type of material
or fuel involved. The type of fire determines the type of extinguisher that
should be used to extinguish it.
1) Class A fires involve materials such as wood,
paper, and cloth which produce glowing embers or char.
2) Class B fires involve flammable gases, liquids,
and greases, including gasoline and most hydrocarbon liquids which must be
vaporized for combustion to occur.
3) Class C fires involve fires in live electrical
equipment or in materials near electrically powered equipment.
4) Class D fires involve combustible metals, such as
magnesium, zirconium, potassium, and sodium.
Extinguishers
will be selected according to the potential fire hazard, the construction and
occupancy of facilities, hazard to be protected, and other factors pertinent to
the situation.
B. Location and Marking of Extinguishers
Extinguishers
will be conspicuously located and readily accessible for immediate use in the
event of fire. They will be located along normal paths of travel and egress.
Wall recesses and/or flush-mounted cabinets will be used as extinguisher
locations whenever possible.
Extinguishers
will be clearly visible. In locations where visual obstruction cannot be
completely avoided, directional arrows will be provided to indicate the
location of extinguishers and the arrows will be marked with the extinguisher
classification.
If
extinguishers intended for different classes of fire are located together, they
will be conspicuously marked to ensure that the proper class extinguisher
selection is made at the time of a fire. Extinguisher classification markings
will be located on the front of the shell above or below the extinguisher
nameplate. Markings will be of a size and form to be legible from a distance of
3 feet.
C. Condition
Portable
extinguishers will be maintained in a fully charged and operable condition.
They will be kept in their designated locations at all times when not being
used. When extinguishers are removed for maintenance or testing, a fully
charged and operable replacement unit will be provided.
D. Mounting and Distribution of Extinguishers
Extinguishers
will be installed on hangers, brackets, in cabinets, or on shelves.
Extinguishers having a gross weight not exceeding 40 pounds will be so
installed that the top of the extinguisher is not more than 3-1/2 feet above
the floor.
Extinguishers
mounted in cabinets or wall recesses or set on shelves will be placed so that
the extinguisher operating instructions face outward. The location of such
extinguishers will be made conspicuous by marking the cabinet or wall recess in
a contrasting color which will distinguish it from the normal decor.
Extinguishers
must be distributed in such a way that the amount of time needed to travel to
their location and back to the fire does not allow the fire to get out of
control. OSHA requires that the travel distance for Class A and Class D
extinguishers not exceed 75 feet. The maximum travel distance for Class B
extinguishers is 50 feet because flammable liquid fires can get out of control
faster that Class A fires. There is no maximum travel distance specified for
Class C extinguishers, but they must be distributed on the basis of appropriate
patterns for Class A and B hazards.
E. Inspection and Maintenance
Once
an extinguisher is selected, purchased, and installed, it is the responsibility
of the CDC Office of Health and Safety to oversee the inspection, maintenance, and
testing of fire extinguishers to ensure that they are in proper working
condition and have not been tampered with or physically damaged.
Fire Safety Inspections/Housekeeping
First
line supervisors and Safety Committees are responsible for conducting work site
surveys at least annually. These surveys should include observations of
worksite safety and housekeeping issues and should specifically address proper
storage of chemicals and supplies, unobstructed access to fire extinguishers,
and emergency evacuation routes. Also, they should determine if an emergency
evacuation plan is present in work areas and that personnel are familiar with
the plan.
Emergency Egress
Every
exit will be clearly visible, or the route to it conspicuously identified in such
a manner that every occupant of the building will readily know the direction of
escape from any point. At no time will exits be blocked.
Any
doorway or passageway which is not an exit or access to an exit but which may
be mistaken for an exit, will be identified by a sign reading "Not An
Exit" or a sign indicating it actual use (i.e., "Storeroom").
Exits and accesses to exits will be marked by a readily visible sign. Each exit
sign (other than internally illuminated signs) will be illuminated by a reliable
light source providing not less than 5 foot-candles on the illuminated surface.
Facilities
will be designed in a manner consistent with health and safety regulations and
standards of good design. The Engineering Services Office, together with OHS,
will ensure that there is appropriate health and safety review of facility
concepts, designs, and plans. A formal design review process is currently in
place for all new construction efforts. ]
Occupant Emergency Plan for Persons with Disabilities
The
first line supervisor is assigned the responsibility to assist Persons with
Disabilities under their supervision. An alternate assistant will be chosen by
the supervisor. The role of the two assistants is to report to their assigned
person, and to either assist in evacuation or assure that the PWD is removed
from danger.
A. Fire Alarms
In
the event of a fire emergency, a fire alarm will sound for the building.
B. Evacuation Routes and Plans
Each
facility shall have an emergency evacuation plan. All emergency exits shall
conform to NFPA standards.
Should
evacuation be necessary, go to the nearest exit or stairway and proceed to an
area of refuge outside the building. Most stairways are fire resistant and
present barriers to smoke if the doors are kept closed.
Do
not use elevators. Should the fire involve the control panel of the elevator or
the electrical system of the building, power in the building may be cut and you
could be trapped between floors. Also, the elevator shaft can become a flue,
lending itself to the passage and accumulation of hot gases and smoke generated
by the fire.
C. Emergency Coordinators
Emergency
Coordinators will be responsible for verifying personnel have evacuated from their
assigned areas.
Fire
Emergency Procedures
If
you discover a fire:
Fight
the fire ONLY if:
If
you hear a fire alarm:
Evacuation
Routes
Sources: Adapted from CDC Fire Safety Manual
Copyright ©2000-2019 Geigle Safety Group, Inc. All rights reserved. Federal copyright prohibits unauthorized reproduction by any means without permission. Disclaimer: This material is for training purposes only to inform the reader of occupational safety and health best practices and general compliance requirement and is not a substitute for provisions of the OSH Act of 1970 or any governmental regulatory agency. CertiSafety is a division of Geigle Safety Group, Inc., and is not connected or affiliated with the U.S. Department of Labor (DOL), or the Occupational Safety and Health Administration (OSHA).